Matavimo kategorija
CAT III 300 V / CAT II 400 V in accordance with DIN EN 61010-1 and DIN EN 61010-2-030
Nominalus srovės diapazonas
0 A AC ... 1 A AC
0 A AC ... 5 A AC
Matavimo diapazonas
0 A AC ... 1.2 A AC
0 A AC ... 6 A AC
0 V AC ... 440 V AC (conductor-neutral conductor, not phase to phase)
0 V AC ... 760 V AC (conductor-conductor, phase to phase)
Overload
1.2 times the nominal value
1.4 times continuous; 150 A for 10 ms
Tolerancija, santykinė
0.25 % (of the nominal value)
3200 samples/s
Prijungimo būdas
Inline data jumper
Spring-cage connection
Kabelio ilgis
The maximum cable length is limited by the conductor cross-section and current transformer. Conductor cross-section: max. 1.5 mm². Maintain this maximum value even if the current transformer supports larger conductor cross-sections for the secondary
Ilgio kodas (šešioliktainis)
Nominalus įtampos diapazonas
0 V AC ... 400 V AC (conductor-neutral conductor, not phase to phase)
0 V AC ... 690 V AC (conductor-conductor, phase to phase)
Registro ilgis (magistralė)
Reikalingi parametrų duomenys
Reikalingi konfigūracijos duomenys
Įvesties pavadinimas
Current measuring input
Voltage measuring input
Įėjimo aprašymas
Detection of I1 ... I3 and IN currents, up to 6 A AC can be connected directly
Veikimo režimas
Process data mode with 12 words, PCP with 2 words
Diagnostikos pranešimai
Measuring circuit fault I/O error message
One line conductor not connected or wire break at line conductor I/O error message
Two line conductors confused I/O error message
Value range for other settings exceeded I/O error message
Value range for transformer factors exceeded I/O error message
Pervoltos kategorija
III (up to 300 V), II (up to 400 V)
Užterštumo laipsnis
2 (IEC 60664-1, EN 60664-1)
Maksimali galios išsklaida nominaliomis sąlygomis
Maitinimo įtampa
7.5 V DC (via voltage jumper)
Laido skerspjūvis, standus
Lankstaus laidininko skerspjūvis
Izoliacijos nuėmimo ilgis
Aplinkos temperatūra (darbinė)