CCCex pastaba
Use in potentially explosive areas is not permitted in China.
MTTF
155 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
378 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
831 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
MTBF
253 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
38 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
Maksimali galios išsklaida nominaliomis sąlygomis
Bandymo įtampos duomenų sąsaja / maitinimo šaltinis
1.5 kVrms (50 Hz, 1 min.)
Maitinimo įtampos diapazonas
11 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
Nominali maitinimo įtampa
Maks. srovės suvartojimas
≤ 2 A (For operation in a joining station, via the DIN rail connector)
Būsenos ir diagnostikos indikatoriai
LEDs: VCC (supply voltage), NET (Mod/Net status), FO signal (fiber optic signal quality), ERR (broken fiber, fiber optic)
Kontaktų perjungimo tipas
Minimali perjungimo įtampa
Maksimali perjungimo įtampa
Ribojamas nuolatinis srovės stipris
Prisukimo sukimo momentas
Bitų iškraipymas, įvestis
Bitų iškraipymas, išėjimas
Rekomenduojamas
± 1 kV
± 2 kV
CAN
CANopen®
DeviceNet™
Minimali perdavimo talpa
-14.6 dBm (62,5/125 µm)
-17.6 dBm (50/125 µm)
-4 dBm (200/230 µm)
Duomenų perdavimo protokolas
Protocol transparent for CAN interface
Prijungimo būdas
B-FOC (ST®)
COMBICON plug-in screw terminal block
Minimalus imtuvo jautrumas
-28.1 dBm (200/230 µm)
-29 dBm (50/125 µm)
-29 dBm (62,5/125 µm)
Perdavimo terpė
2-wire twisted pair, shielded
Multi-mode fiberglass
PCF fiber
Perdavimo greitis
≤ 1 Mbps (Configurable via DIP switches)
Perduodamo signalo ilgis
≤ 5000 m (Dependent on the data rate and the protocol used)
Magistralės įrenginių skaičius
≤ 128 (CANopen®, can be addressed logically)
≤ 63 (DeviceNet™, can be addressed logically)
≤ 64 (per potential segment)
Uždarymo rezistorius
124 Ω (Integrated and ready to be switched)
Viengyslis laidininkas/jungimo taškas, nelankstus
Viengyslis/jungimo taškas, lankstus
Maks. lanksčiojo laidininko skerspjūvio plotas pagal AWG
Min. AWG laidininko skerspjūvis, lankstus
Viengyslis laidas/jungimo taškas, standus, AWG maks.
Viengyslis/gnybtas, standus, AWG min.
Izoliacijos nuėmimo ilgis
Pluošto tipai
200/230 µm
50/125 µm
62.5/125 µm
Fiberglass
PCF fiber