Naudojimo pastabos
Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Montavimo pastaba
in rows with zero spacing
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
Tipinė įėjimo srovė esant UN
7 mA (50 Hz)
8 mA (60 Hz)
Pritaikymas
Filter to prevent interference
Mechaninis tarnavimo laikas
Izoliacija
Safe isolation, reinforced insulation
Paskutinio duomenų tvarkymo data
Maksimali galios išsklaida nominaliomis sąlygomis
Bandymo įtampa (apvija/kontaktas)
4 kVrms (50 Hz, 1 min., winding/contact)
Nominali izoliacijos įtampa
Nominali viršįtampio įtampa
Vardinė įėjimo įtampa U N
Įėjimo įtampos diapazonas
85.8 V DC ... 154 V DC (20 °C)
93.6 V AC ... 168 V AC (20 °C)
Vardinė įtampa (prijungtas elektromechaninis relė)
Tipinė įėjimo srovė esant U < sub > N < /sub >
7 mA (50 Hz)
8 mA (60 Hz)
Apsauginė grandinė
Bridge rectifier
RC element
Kontaktų perjungimo tipas
Maksimali perjungimo įtampa
Minimali perjungimo įtampa
Ribojamas nuolatinis srovės stipris
Trumpojo jungimo srovė
200 A (conditional short-circuit current)
Maks. pertraukimo galia (omine apkrova)
140 W (24 V DC)
1500 VA (250 V AC)
18 W (60 V DC)
20 W (48 V DC)
23 W (110 V DC)
40 W (220 V DC)
Minimali perjungimo galia
Perjungimo galia
0.1 A (at 220 V, DC13)
0.2 A (at 110 V, DC13)
2 A (at 24 V, DC13)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)
3 A (at 24 V, AC15)
Izoliacijos nuėmimo ilgis
Laido skerspjūvio plotas (fiksuotas)
Lankstaus laidininko skerspjūvis
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)