Naudojimo pastabos
Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Montavimo pastaba
in rows with zero spacing
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
Tipinė įėjimo srovė esant UN
Mechaninis tarnavimo laikas
Izoliacija
Safe isolation, reinforced insulation
Paskutinio duomenų tvarkymo data
Maksimali galios išsklaida nominaliomis sąlygomis
Bandymo įtampa (apvija/kontaktas)
4 kV AC (50 Hz, 1 min., winding/contact)
Nominali izoliacijos įtampa
Nominali viršįtampio įtampa
Vardinė įėjimo įtampa U N
Įėjimo įtampos diapazonas
10.32 V DC ... 16.8 V DC (20 °C)
Vardinė įtampa (prijungtas elektromechaninis relė)
Tipinė įėjimo srovė esant U < sub > N < /sub >
Apsauginė grandinė
Reverse polarity protection; Polarity protection diode
Surge protection; Freewheeling diode
Kontaktų perjungimo tipas
Maksimali perjungimo įtampa
250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimali perjungimo įtampa
Ribojamas nuolatinis srovės stipris
10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged)
6 A
Maksimali įjungimo srovė
130 A (peak, at capacitive load, 230 V AC, 24 μF)
80 A (20 ms)
Maks. pertraukimo galia (omine apkrova)
144 W (at 24 V DC)
1500 VA (for 250 V AC)
48 W (at 60 V DC)
50 W (at 110 V DC)
58 W (at 48 V DC)
80 W (at 220 V DC)
85 W (for 250 V DC)
Pertraukimo vardinė vertė (omine apkrova) maks. sujungus
240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.)
2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.)
Minimali perjungimo galia
Perjungimo galia
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
2 A (at 24 V, DC13)
6 A (at 120 V, AC15)
6 A (at 24 V, AC15)
6 A (at 250 V, AC15)
Izoliacijos nuėmimo ilgis
Laido skerspjūvio plotas (fiksuotas)
Lankstaus laidininko skerspjūvis
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Degumo klasė pagal UL 94 (korpusas)