Input voltage range in reference to UN
Typical input current at UN
Pollution degree
2 (Rated voltage of 230/400 V)
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
2.5 kVrms (50 Hz, 1 min., winding/contact)
Test voltage (Contact/contact)
2.5 kVrms (50 Hz, 1 min., contact/contact)
Input voltage range
184 V AC ... 276 V AC (20 °C)
Input voltage range in reference to UN
Typical input current at UN
Typical release time range
Operating voltage display
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
30 A (20 ms, N/O contacts)
Interrupting rating (ohmic load) max.
108 W (at 60 V DC)
124 W (at 48 V DC)
204 W (at 24 V DC)
2125 VA (for 250 V AC)
48 W (at 220 V DC)
52 W (at 110 V DC)
Switching capacity
0.11 A (at 250 V, DC13)
0.22 A (at 120 V, DC13)
1.5 A (at 240 V, AC15)
2 A (at 24 V, DC13)
3 A (at 120 V, AC15)
Conductor cross-section rigid
Conductor cross-section flexible
0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
Conductor cross-section AWG
26 ... 16 (flexible)
26 ... 16 (solid)
Flammability rating according to UL 94 (Housing)