Typ. starting time with Us
typ. 10 ms (with Us when controlled via A1)
Rated control circuit supply voltage US
24 V AC/DC -20 % ... +10 %
Application
High demand
Low demand
Safe switch off
Rated control supply current IS
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typ. starting time with Us
typ. 10 ms (with Us when controlled via A1)
Typical release time
typ. 10 ms (with Us when controlled via A1)
Maximum power dissipation for nominal condition
8.71 W (at UB = 26.4 V DC, US = 24 V, IS = 52 mA, n = 1, IL² = 72 A², Rcontact = 0.1 )
Rated surge voltage/insulation
Basic insulation 4 kV between all output current paths
Rated control circuit supply voltage US
24 V AC/DC -20 % ... +10 %
Rated control supply current IS
Filter time
1 ms (at A1-A2; test pulse width)
1 s (at A1-A2; test pulse rate)
Contact switching type
2 confirmation current paths
4 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 5 V AC/DC
Switching capacity
5 A (AC15, 250 V)
5 A (DC13, 24 V)
Limiting continuous current
Interrupting rating (ohmic load) max.
Maximum interrupting rating (inductive load)
33 W (N/O contact, 220 V DC, τ = 40 ms)
35 W (N/O contact, 110 V DC, τ = 40 ms)
36 W (N/O contact, 60 V DC, τ = 40 ms)
40 W (N/O contact, 48 V DC, τ = 40 ms)
48 W (N/O contact, 24 V DC, τ = 40 ms)
Output fuse
10 A gL/gG NEOZED
4 A gL/gG NEOZED (Low demand)
6 A gL/gG NEOZED
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section, flexible, with ferrule, with plastic sleeve
0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section, flexible, with ferrule, without plastic sleeve
0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG
Operating voltage display