Typ. starting time with Us
125 ms (when controlled via A1)
Rated control circuit supply voltage US
Rated control supply current IS
Application
Emergency stop
Light grid
Safety door
Mechanical service life
10x 106 cycles
approx. 107 cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typical response time
110 ms (manual, monitored start)
125 ms (automatic start)
Typ. starting time with Us
125 ms (when controlled via A1)
Typical release time
10 ms (on demand via the sensor circuit)
45 ms (on demand via A1)
Recovery time
1 s (following demand of the safety function)
Maximum power dissipation for nominal condition
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Rated control circuit supply voltage US
Rated control supply current IS
Inrush current
< 3.5 A (typ. with US, Δt = 3 ms)
< 6 mA (typ. with US at S34/35, Δt = 70 ms)
max. 110 mA (typ. with US, Δt = 3 ms)
max. 6 A
min. 10 mA
Filter time
5 ms (in the event of voltage dips at Us)
max. 2 ms (Test pulse width low test pulses, at 100 ms test pulse rate)
No brightness test pulses / high test pulses permitted.
No test pulses permitted
Protective circuit
Serial protection against polarity reversal; Suppressor diode
Suppressor diode
Description of the input
non-safety-related
safety-related
Input voltage range "0" signal
Input voltage range "1" signal
Input current range "0" signal
Max. permissible overall conductor resistance
Current consumption
0 mA (typ. with US at S34)
1 mA (typ. with US at S35)
38 mA (typ. with US at S12/S22)
Output description
2 N/C contacts parallel, non-safety-related, floating
2 N/O contacts each in series, safety-related, floating
Contact switching type
1 signaling current path
3 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 10 V
min. 10 V AC/DC
Switching capacity
1.5 A (AC15)
2 A (DC13)
5 A (AC15)
6 A (DC13)
Limiting continuous current
6 A
6 A (Observe derating and load limit curve)
Sq. Total current
36 A2 (observe derating)
72 A2 (observe derating)
Output fuse
10 A gL/gG
4 A gL/gG (for low-demand applications)
6 A gL/gG