Rated control circuit supply voltage US
Rated control supply current IS
Application
Emergency stop
Safety door
Mechanical service life
10x 106 cycles
approx. 107 cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typical response time
typ. 100 ms (For Us manual, monitored start)
Typical release time
typ. 20 ms (At Us on demand via sensor circuit)
typ. 45 ms (At Us/on demand via A1)
Restart time
< 1 s (Boot time, after switching on the supply voltage)
Recovery time
1 s (following demand of the safety function)
500 ms (Availability time after activating the sensor circuit during manual start)
Start pulse length
min. 500 ms (manual start)
Maximum power dissipation for nominal condition
16.44 W (US = 26.4 V, IL² = 72 A², PTotal max = 2.04 W + 14.4 W)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Rated control circuit supply voltage US
Rated control supply current IS
Inrush current
< 100 mA (typ. with US at S12)
< 3.5 A (typ. with US, Δt = 3 ms)
< 6 mA (typ. with US at S34)
> -100 mA (typ. with US at S22)
max. 6 A
min. 10 mA
Filter time
5 ms (in the event of voltage dips at Us)
No test pulses permitted
Protective circuit
Serial protection against polarity reversal
Suppressor diode
Description of the input
non-safety-related
safety-related
Input voltage range "0" signal
Input voltage range "1" signal
20.4 V ... 26.4 V
20.4 V ... 26.4 V (S12)
Input current range "0" signal
Max. permissible overall conductor resistance
Current consumption
-38 mA (typ. with US at S22)
1 mA (typ. with US at S34)
38 mA (typ. with US at S12)
Output description
2 N/C contacts parallel, non-safety-related, floating
2 N/O contacts in series, safety-related, floating
Contact switching type
1 signaling current path
2 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 10 V AC/DC
Switching capacity
1.5 A (AC15)
2 A (DC13)
5 A (AC15)
6 A (DC13)
Limiting continuous current
6 A
6 A (Signaling current path)
Sq. Total current
36 A2
72 A2 (observe derating)
Output fuse
10 A gL/gG (High demand)
4 A gL/gG (Low demand)
6 A gL/gG
Conductor cross-section rigid
Conductor cross-section flexible