Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC -20 % ... +40 %
Inrush current integral (I2t)
Frequency range (fN)
16.7 Hz (acc. to EN 50163)
50 Hz ... 60 Hz -10 % ... +10 %
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (constant capacity)
Typical national grid voltage
Nominal output current (IN)
Voltage type of supply voltage
Static Boost (IStat.Boost)
Dynamic Boost (IDyn.Boost)
5 A (≤60 °C (5 s), Input <150 V AC Derating 0.5 %/V)
Inrush current integral (I2t)
Inrush current limitation
< 10 A
4.3 A (after 1 ms)
POut
> PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
Frequency range (fN)
16.7 Hz (acc. to EN 50163)
50 Hz ... 60 Hz -10 % ... +10 %
UOut
< 0.9 x USet (LED flashes green)
> 0.9 x USet (LED lights up green)
Mains buffering time
typ. 54 ms (120 V AC)
typ. 54 ms (230 V AC)
Current consumption
0.33 A (250 V DC)
0.37 A (240 V AC)
0.39 A (230 V AC)
0.7 A (120 V AC)
0.75 A (110 V DC)
0.85 A (100 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
3.15 A (slow-blow, internal)
Recommended breaker for input protection
6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE
< 0.25 mA (264 V AC, 60 Hz)
0.22 mA (264 V AC, 60 Hz)
Efficiency
typ. 91.9 % (120 V AC)
typ. 92.6 % (230 V AC)
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
5 A (≤60 °C (5 s), Input <150 V AC Derating 0.5 %/V)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Residual ripple
< 40 mVPP (with nominal values)
Maximum no-load power dissipation
< 1 W (120 V AC)
< 1 W (230 V AC)
Power loss nominal load max.
< 5 W (120 V AC)
< 5 W (230 V AC)
Crest factor
typ. 1,82 (230 V AC)
typ. 1.69 (120 V AC)
Rise time
50 ms (UOut = 10 % ... 90 %)
Connection in parallel
yes, for redundancy and increased capacity
Default
24 V DC 30 mA 24 V DC for UOut > 0.9 x USet
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.