Typ. starting time with Us
300 ms (when controlled via A1 or S11/S12)
Rated control circuit supply voltage US
Rated control supply current IS
Application
Emergency stop
Safety door
Mechanical service life
10x 106 cycles
approx. 107 cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Overvoltage category
II, III (See the section “Insulation coordination”)
Typical response time
300 ms (automatic start)
50 ms (manual, monitored start)
Typ. starting time with Us
300 ms (when controlled via A1 or S11/S12)
Typical release time
150 ms (when controlled via A1)
20 ms (when controlled via S11/S12)
Maximum power dissipation for nominal condition
16.4 W (At IL² = 72 A²,PTotal max = 2 W + 14.4 W)
Rated surge voltage/insulation
4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV between A1-A2/logic/enabling and signaling current paths)
Rated control circuit supply voltage US
Rated control supply current IS
Protective circuit
Surge protection; Suppressor diode
Description of the input
non-safety-related
safety-related
Max. permissible overall conductor resistance
Number of outputs
1 (undelayed)
3 (undelayed)
Contact switching type
1 signaling current path
3 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 10 V AC/DC
Switching capacity
5 A (230 V (AC15))
6 A (24 V (DC13))
Limiting continuous current
5 A
6 A (observe derating)
Sq. Total current
72 A2
72 A2 (observe derating)
Output fuse
10 A gL/gG NEOZED
6 A gL/gG NEOZED
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Operating voltage display