Inrush current integral (I2t)
Nominal input voltage range
Input voltage range
2x 360 V AC ... 575 V AC
3x 320 V AC ... 575 V AC
450 V DC ... 800 V DC
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
5 A (-25 °C ... 60 °C, UOUT = 24 V DC)
Voltage type of supply voltage
POWER BOOST (IBoost)
7.5 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
Inrush current integral (I2t)
Selective Fuse Breaking (ISFB)
Mains buffering time
> 20 ms (400 V AC)
> 30 ms (500 V AC)
Current consumption
0.2 A (600 V DC)
3x 0.7 A (500 V AC)
3x 0.8 A (400 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Permissible DC backup fuse
DC: Connect a suitable fuse upstream
Recommended breaker for input protection
6 A ... 16 A (AC: Characteristics B, C, D, K)
Efficiency
> 89 % (at 400 V AC and nominal values)
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
5 A (-25 °C ... 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost)
7.5 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB)
Magnetic circuit breaker tripping
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Residual ripple
< 20 mVPP (with nominal values)
Peak switching voltages nominal load
< 20 mVPP (at nominal values, 20 MHz)
Maximum no-load power dissipation
Power loss nominal load max.
Rise time
< 0.04 s (UOUT (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Output description
IOUT < IN: High signal
Relay contact, UOUT > 0.9 x UN: Contact closed
UOUT > 0.9 x UN: High signal
Maximum inrush current
≤ 20 mA (short-circuit-proof)
0.5 A
1 A
Maximum switching voltage
Connection method
Pluggable screw connection
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.