Nominal input voltage UIN
Nominal input current at UIN
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Connection method
Bus base module
Push-in connection
Required configuration data
Input voltage range "0" signal
Input voltage range "1" signal
Nominal input voltage UIN
Nominal input current at UIN
Protective circuit
Polarity reversal protection of the inputs; parallel diode (30 V, 5 s)
Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning)
Surge protection; electronic (35 V, 0.5 s)
Mounting position
any (no temperature derating)
Scope of supply
including bus base module and Axioline F connectors
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Current draw
max. 120 mA (up to HW 01)
max. 30 mA
max. 60 mA (from HW 02)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Protection
max. 8 A (polarity reversal protection up to 5 A)
Test voltage: 5 V supply of the local bus / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Test voltage: 24 V supply (I/O) / functional ground
Note on the connection method
Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual.
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG