Typ. starting time with Us
< 250 ms (when controlled via A1)
Rated control circuit supply voltage US
20.4 V DC ... 26.4 V DC
24 V DC -15 % / +10 %
Rated control supply current IS
Application
Emergency stop
Light grid
Magnetic switch
Safety door
Transponder
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typical response time
< 175 ms (automatic start)
< 175 ms (manual, monitored start)
Typ. starting time with Us
< 250 ms (when controlled via A1)
Typical release time
< 20 ms (on demand via A1)
< 20 ms (on demand via the sensor circuit)
Maximum power dissipation for nominal condition
4.8 W (US = 26.4 V, IL² = 48 A², PTotal max = 2.4 W + 2.4 W)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Rated control circuit supply voltage US
20.4 V DC ... 26.4 V DC
24 V DC -15 % / +10 %
Rated control supply current IS
Inrush current
< 20 mA (typ. with US at S12)
< 5 mA (typ. with US at S22)
max. 6 A
min. 3 mA
typ. 200 mA (typ. with US)
typ. 5 A (Δt = 200 µs at Us)
Filter time
1 ms (at A1 in the event of voltage dips at Us)
max. 1.5 ms (Test pulse width of low test pulses)
Test pulse rate = 5 x Test pulse width
Protective circuit
Serial protection against polarity reversal; Suppressor diode
Suppressor diode
Description of the input
non-safety-related
safety-related sensor inputs
Input voltage range "0" signal
0 V DC ... 5 V DC (for safe Off; at S12 and S22)
Input current range "0" signal
0 mA ... 2 mA (for safe Off; at S12 and S22)
Max. permissible overall conductor resistance
Current consumption
< 10 mA (typ. with US at S34/24 V)
< 5 mA (typ. with US)
> -5 mA (typ. with US at S34/0 V)
Input voltage range "1" signal
Output description
2 N/O contacts each in series, safety-related, floating
non-safety-related
Number of outputs
1 (digital, PNP)
3 (undelayed)
Switching voltage
max. 250 V AC/DC
min. 12 V AC/DC
Limiting continuous current
Output fuse
4 A gL/gG (for low-demand applications)
6 A gL/gG