Derating IStat. Boost
< 100 V AC (1 %/V)
< 110 V DC (1 %/V)
Nominal input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Inrush current integral (I2t)
Derating IStat. Boost
< 100 V AC (1 %/V)
< 110 V DC (1 %/V)
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
POWER BOOST (IBoost)
15 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
Voltage type of supply voltage
Selective Fuse Breaking (ISFB)
Inrush current integral (I2t)
Inrush current limitation
Mains buffering time
typ. 36 ms (120 V AC)
typ. 36 ms (230 V AC)
Current consumption
1.5 A (250 V DC)
1.7 A (240 V AC)
3.4 A (110 V DC)
4 A (100 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Input fuse
10 A (slow-blow, internal)
Recommended breaker for input protection
10 A ... 20 A (Characteristics B, C, D, K)
Efficiency
typ. 92 % (120 V AC)
typ. 93.2 % (230 V AC)
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
POWER BOOST (IBoost)
15 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB)
Magnetic circuit breaker tripping
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
Residual ripple
< 50 mVPP (with nominal values)
Maximum no-load power dissipation
Power loss nominal load max.
Rise time
< 0.05 s (UOUT (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Output description
IOUT < IN: High signal
Relay contact, UOUT > 0.9 x UN: Contact closed
UOUT > 0.9 x UN: High signal
Maximum inrush current
0.5 A (ATEX/IECEx: Ohmic loads only)
1 A (ATEX/IECEx: Ohmic loads only)
20 mA (short-circuit-proof)
Maximum switching voltage