Typ. starting time with Us
< 70 ms (with control via control input 3)
Rated control circuit supply voltage US
24 V DC -10 % ... +10 % (“1” signal)
Rated control supply current IS
Application
High demand
Low demand
Safe switch off
Safe switch on
Relay type
Electromechanical relay in accordance with IEC/EN 61810
Typ. starting time with Us
< 70 ms (with control via control input 3)
Typical release time
< 50 ms (with request via control input 3)
Maximum power dissipation for nominal condition
UB = 26.4 V, US = 24 V, IS = 31 mA, IL² = 48 A, Rcontact = 0.025 Ω
Rated surge voltage/insulation
Rated control circuit supply voltage US
24 V DC -10 % ... +10 % (“1” signal)
Rated control supply current IS
Inrush current
max. 4 A
min. 10 mA
typ. 200 mA (Δt = 5 ms at Us)
Filter time
1 ms (in the event of voltage dips at Us)
Output description
1 N/O contact, undelayed, floating
Switching voltage
max. 250 V AC/DC
min. 12 V DC
Switching capacity
1.2 A (24 V (DC13))
1.6 A (230 V (AC15))
Limiting continuous current
Output fuse
4 A gL/gG (Safe state OFF application)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG