Inrush current integral (I2t)
Maximum altitude (Maximum)
Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
Input voltage range
2x 400 V AC ... 500 V AC ±10 %
3x 400 V AC ... 500 V AC -20 % ... +10 %
Setting range of the output voltage (USet)
Nominal output current (IN)
Typical national grid voltage
Dynamic Boost (IDyn.Boost)
Voltage type of supply voltage
Inrush current integral (I2t)
Output power (PDyn. Boost)
Mains buffering time
typ. 21 ms (3x 400 V AC)
typ. 21 ms (3x 480 V AC)
Current consumption
2x 2.1 A (2x 500 V AC)
2x 2.6 A (2x 400 V AC)
3x 1.2 A (3x 500 V AC)
3x 1.5 A (3x 400 V AC)
Protective circuit
Transient protection; Varistor
Device mains fuse
6.3 A internal (device protection)
Recommended breaker for input protection
3x 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Efficiency
typ. 94.4 % (3x 400 V AC)
typ. 94.6 % (3x 480 V AC)
Setting range of the output voltage (USet)
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
Nominal current per channel
1 A
10 A
2 A
3.8 A
4 A
6 A
8 A
Rated current (pre-adjusted)
Waiting time after switch off of a channel
Switch-on delay of the channels
Crest factor
typ. 1,53 (3x 480 V AC)
typ. 1.54 (3x 400 V AC)
Output power (PDyn. Boost)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Residual ripple
typ. 13 mVPP (with nominal values)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
Rise time
≤ 1 s (UOut = 10 % ... 90 %)
Minimum no-load power dissipation
Maximum no-load power dissipation
Minimum nominal load power dissipation