Inrush current integral (I2t)
Frequency range (fN)
50 Hz ... 60 Hz -10 % ... +10 %
Nominal input voltage range
± 260 V DC ... 300 V DC
2x 400 V AC ... 500 V AC
3x 400 V AC ... 500 V AC
Input voltage range
± 260 V DC ... 300 V DC -13 % ... +30 %
2x 400 V AC ... 500 V AC -10 % ... +10 %
3x 400 V AC ... 500 V AC -20 % ... +10 %
520 V DC ... 600 V DC -13 % ... +30 % (mid-point earthed)
Setting range of the output voltage (USet)
24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN)
Typical national grid voltage
Static Boost (IStat.Boost)
Voltage type of supply voltage
Dynamic Boost (IDyn.Boost)
Inrush current integral (I2t)
Selective Fuse Breaking (ISFB)
Inrush current limitation
POut
> 100 % (LED lights up yellow, output power > 480 W)
> 50 % (LED lights up green, output power > 240 W)
> 75 % (LED lights up green, output power > 360 W)
AC frequency range
50 Hz ... 60 Hz -10 % ... +10 %
UOut
< 0.9 x USet (LED flashes green)
> 0.9 x USet (LED lights up green)
Frequency range (fN)
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
typ. 33 ms (3x 400 V AC)
typ. 33 ms (3x 480 V AC)
Current consumption
1.06 A (±300 V DC)
1.23 A (± 260 V DC)
2x 1.23 A (500 V AC)
2x 1.37 A (480 V AC)
2x 1.62 A (400 V AC)
3x 0.8 A (500 V AC)
3x 0.81 A (480 V AC)
3x 0.99 A (400 V AC)
Reverse polarity protection
Nominal power consumption
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Recommended breaker for input protection
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
3x 4 A ... 20 A (Characteristic B, C or comparable)
Recommended fuse for input protection
Discharge current to PE
< 3.5 mA
1.7 mA (550 V AC, 60 Hz)
Efficiency
typ. 94.1 % (400 V AC)
typ. 94.9 % (480 V AC)
Setting range of the output voltage (USet)
24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
Selective Fuse Breaking (ISFB)
Magnetic circuit breaker tripping
A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating
> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.25 % (change in input voltage ±10 %)
< 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Residual ripple
< 60 mVPP (with nominal values)
Apparent power
686 VA (400 V, UOUT = 24 V, IOUT = stat. Boost)
698 VA (480 V, UOUT = 24 V, IOUT = stat. Boost)
Maximum no-load power dissipation
< 6 W (400 V AC)
< 6 W (480 V AC)
Power loss nominal load max.
< 30 W (400 V AC)
< 30 W (480 V AC)