Rated control circuit supply voltage US
Rated control supply current IS
typ. 20 mA
typ. 20 mA (Outputs active, without load)
Restart time
max. 10 s (Boot time)
min. 5 s (Boot time)
Maximum power dissipation for nominal condition
1.82 W (with max. permissible load)
Interfaces
DIN rail TBUS for connection to the master module, supplied as standard
Rated surge voltage/insulation
Rated control circuit supply voltage US
Rated control supply current IS
typ. 20 mA
typ. 20 mA (Outputs active, without load)
Inrush current
1.5 A (Δt = 1 ms at Us)
2 A (Δt = 1 ms at Us)
Filter time
typ. 1 ms (in the event of voltage dips)
typ. 5 ms (at A1 in the event of voltage dips at Us)
Protective circuit
Inverse-parallel protection against polarity reversal
Serial protection against polarity reversal
Suppressor diode
Output description
non-safety-related
PNP, IEC 61131-2 Typ 0,1
Reference ground A2
Output voltage when switched off
Output voltage range
18.2 V DC ... 27.8 V DC (US - 1 V)
Limiting continuous current
100 mA (per channel)
400 mA (Total current of all digital signal outputs)
Ohmic load
min. 180 Ω (Observe limiting continuous current)
Short-circuit protection
Yes (self-limitation at 1.1 A)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Status display
1 x LED (green), 2 x LED (orange)
8 x LED (yellow)
Operating voltage display