Rated control circuit supply voltage US
Rated control supply current IS
Restart time
max. 10 s (Boot time)
min. 5 s (Boot time)
Maximum power dissipation for nominal condition
Interfaces
DIN rail TBUS for connection to the master module, supplied as standard
Rated surge voltage/insulation
Rated control circuit supply voltage US
Rated control supply current IS
Inrush current
2 A (Δt = 1 ms at Us)
max. 6 A
min. 20 mA
Filter time
250 ms ±2 ms (Test pulse rate > 500 ms)
typ. 5 ms (at A1 in the event of voltage dips at Us)
Protective circuit
Serial protection against polarity reversal
Input voltage range "0" signal
Input voltage range "1" signal
Input current range "0" signal
Max. permissible overall conductor resistance
1.2 kΩ (Input and reset circuit at US)
Current consumption
max. 13 mA (at a control voltage of 28.8 V DC)
typ. 10 mA (typ. with US)
Output description
safety-related N/O contacts
Switching voltage
max. 250 V AC/DC (Observe the load curve)
min. 10 V AC/DC
Switching capacity
2 A (24 V (DC13))
3 A (250 V (AC15))
Limiting continuous current
Sq. Total current
32 A2 (for 2 x 2-channel, observe derating)
64 A2 (with 4 x 1-channel, observe derating)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG