Max. internal capacitance Ci
Max. output current Io
16.8 mA (TC with external cold junction compensation)
4.3 mA (mV)
7.1 mA (TC with internal cold junction compensation)
7.1 mA (TC without cold junction)
Max. output power Po
11 mW (TC with internal cold junction compensation)
11 mW (TC without cold junction)
25.2 mW (TC with external cold junction compensation)
6.5 mW (mV)
Safety-related maximum voltage Um
110 V DC (≤ 2000 m)
121 V AC (≤ 2000 m)
121 V AC/DC (> 2000 m ... 3000 m)
30 V DC (Zone 2: CHn+, CHn-)
33 V AC/DC (> 4000 m ... 5000 m)
60 V AC/DC (> 3000 m ... 4000 m)
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co
Electrical isolation between input and output
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co
Typical cold point errors
IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co
100 mH / 950 nF, 50 mH / 950 nF, 5 mH / 950 nF, 1 mH / 950 nF
Step response (0–99%)
≤ 1.7 s (with filter factor = 1)
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co
100 mH / 555 nF, 50 mH / 555 nF, 5 mH / 555 nF, 1 mH / 555 nF, 10 µH / 555 nF
Maximum temperature coefficient
Transmission error, typical
0.1 % (e.g., for type J, 400 K span, 4 mA ... 20 mA)
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-6-4
GB/T 3836.1
GB/T 3836.3
GB/T 3836.4
IEC/EN 60079-11
IEC/EN 60079-7
IEC/EN 61010-1
Rated insulation voltage
150 Vrms
150 Vrms (Input/output, power supply)
150 Vrms (Input/output/power supply)
162 Vrms (Input/output/power supply)
200 Vrms
212 VP
212 VP (Input/output, power supply)
230 VP (Input/output/power supply)
251 Vrms
355 VP
60 Vrms (Input/output, power supply)
60 Vrms (Input/output/power supply)
84 VP (Input/output, power supply)
84 VP (Input/output/power supply)
Insulation
Double/reinforced insulation
Power dissipation
≤ 0.7 W (Active output)
≤ 1 W (Passive output)
Power consumption
≤ 0.73 W (Passive output)
≤ 1 W (Active output)
Sensor types that can be used (TC)
B, E, J, K, N, R, S, T, L, U, C, D, A, A-1, A-2, A-3, M, Lr
Temperature measuring range
-230 °C ... 2500 °C (Range depending on the sensor type)
≥ 50 K (Thermocouples)
Temperature measuring range: Type B thermocouple
Temperature measuring range: Type E thermocouple
Temperature measuring range: Type J thermocouple
Temperature measuring range: Type K thermocouple
Temperature measuring range: Type N thermocouple
Temperature measuring range: Type R thermocouple
Temperature measuring range: Type S thermocouple
Temperature measuring range: Type T thermocouple
Temperature measuring range: Type L thermocouple
Temperature measuring range: Type U thermocouple
Temperature measuring range: Type C thermocouple
Temperature measuring range: Type D thermocouple
Temperature measuring range: Type A1 GOST thermocouple