Inrush current integral (I2t)
Nominal input voltage range
Input voltage range
12 V DC ... 24 V DC -25 % ... +33 % (SELV)
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN)
Static Boost (IStat.Boost)
Dynamic Boost (IDyn.Boost)
Inrush current integral (I2t)
Inrush current limitation
Output power (PStat. Boost)
Output power (PDyn. Boost)
Current consumption
typ. 3.5 A (24 V DC)
typ. 7.2 A (12 V DC)
Input fuse
15 A (fast blow, internal)
Recommended breaker for input protection
10 A ... 16 A (Characteristic B, C, D, K or comparable)
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
Derating
> 60 °C (2.5%/K of POut nom.)
Output power (PStat. Boost)
Output power (PDyn. Boost)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation static
< 1 % (change in load, static 10 % ... 90 %)
Control deviation dynamic
< 1 % (change in load, static 10 % ... 90 %)
Control deviation Input voltage change
< 1 % (change in load, static 10 % ... 90 %)
Rise time
< 1 s (UOUT (10 % ... 90 %))
Maximum no-load power dissipation
Power loss nominal load max.
Connection in parallel
yes, for redundancy and increased capacity
Fuse protection (secondary side)
rigid
0.2 mm² ... 2.5 mm²
0.5 mm² ... 2.5 mm²
0.75 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
0.5 mm² ... 2.5 mm²
0.75 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
0.5 mm² ... 2.5 mm²
0.75 mm² ... 2.5 mm²